Apple Mac Mouse Settings
- Configure these Apple Mac® mouse settings:
Absolute Mouse Synchronization is required for proper mouse synchronization on KVM target servers running a Mac® operating system.
In order for Absolute Mouse Synchronization to work, a virtual media CIM is required. For a list of supported CIMs, see Supported Computer Interface Module (CIMs) Specifications.
Once you have completed your KX III installation, set the Mac USB profile. If you do not set this profile, the mouse does synch in OS X.
To do this, do one of the following:
- Connect to the Mac target from the Raritan KVM Client.
- Select USB Profile > Other Profiles > Mac OS-X (10.4.9 and later).
Or
- In KX III, select Device Settings > Port Configuration, then click on the target name to open the Port page.
- Expand 'Select USB Profiles for Port' section.
- Select 'Mac OS-X (10.4.9) and later' from the Available box, then click Add to add it to the Selected box.
- Click on 'Mac OS-X (10.4.9) and later' in the Selected box. This automatically adds it to the Preferred Profile drop-down.
- Select 'Mac OS-X (10.4.9) and later' from the Preferred Profile drop-down, then check the checkbox under 'Set Active Profile As Preferred Profile'.